Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| Device application | distribution |
| Suitability for isolation | yes conforming to EN/IEC 60947-2 |
| Trip unit technology | electronic |
| Utilisation category | category B |
| Network type | AC |
| Breaking capacity code | N 50 kA 415 V AC |
| Breaking capacity | 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2, 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mounting mode | fixed |
| Control type | manually operated |
| Range | ComPacT |
| Protected poles description | 3D |
| Range of product | ComPacT NS630b...1600 new generation |
| Trip unit name | MicroLogic 2.0 |
| Poles description | 3P |
| Product name | ComPacT NS new generation |
| Product or component type | circuit breaker |
| Trip unit protection functions | LI |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| [In] rated current | 1600 A at 50 °C |
| Network frequency | 50/60 Hz |
| Complementary | |
| Power losses | 74 W |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| Compatibility code | NS1600 |
| Trip unit rating | 1600-1600 A at 50 °C |
| Long time pick-up adjustment type Ir | adjustable 9 settings |
| Electrical durability | 5000 cycles at 440 V In/2, 2000 cycles at 440 V In, 2000 cycles at 690 V In/2, 1000 cycles at 690 V In |
| Zone selective interlocking ZSI | without |
| Downside connection | front |
| Earth-leakage protection | without |
| Thermal memory | 20 mn |
| Height | 327 mm |
| [Ics] rated service breaking capacity | 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2, 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2, 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2, 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
| [tr] long-time delay adjustment range | 0.7-16.6 s at 7.2 x Ir, 0.5-24 s at 6 x Ir, 12.5-600 s at 1.5 x Ir |
| Net weight | 14 kg |
| Long time delay adjustment type | adjustable 9 settings |
| Auxiliary contact composition | 1 NO/NC |
| [Icw] rated short-time withstand current | 19.2 kA 1 s conforming to IEC 60947-2 |
| Connection pitch | 70 mm |
| Mechanical durability | 10000 cycles |
| Upside connection | front |
| Long time pick-up adjustment range | 0.4...1 x In |
| Protection type | I : for instantaneous short-circuit protection, L : for overload protection (long time) |
| Depth | 147 mm |
| Width | 210 mm |
| Local signalling | 1 LED (yellow) for overload, 4 LEDs (red) for fault indication |
| Instantaneous pick-up adjustment type Ii | adjustable |
| Instantaneous pick-up adjustment range | 1.5...10 x Ir |
| Mounting support | backplate |
| Environment | |
| Relative humidity | 0-95 % |
| Ambient air temperature for storage | -50-85 °C |
| Operating altitude | 2000 m...5000 m with derating, 0...2000 m without derating |
| Product certifications | IECEE CB Scheme |
| Pollution degree | 3 conforming to IEC 60947 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Ambient air temperature for operation | -25-70 °C |
| IK degree of protection | IK07 conforming to EN 50102 |
| Standards | EN/IEC 60947-2 |