Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| [Ue] rated operational voltage | 240 V AC 50/60 Hz |
| Poles description | 1P + N |
| Range | MAX9 |
| Product or component type | residual current breaker with overcurrent protection (RCBO) |
| Earth-leakage sensitivity | 30 mA |
| Earth-leakage protection class | type A |
| Network type | AC |
| Number of protected poles | 1 |
| Curve code | C |
| [In] rated current | 25 A at 30 °C conforming to AS/NZS 61009.1 |
| Network frequency | 50/60 Hz |
| Complementary | |
| Depth | 73 mm |
| Width | 18 mm |
| [Uimp] rated impulse withstand voltage | 4 kV |
| Grid distance | 45 mm |
| Breaking capacity | 6000 A Icn at 240 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 440 V AC 50/60 Hz |
| Earth-leakage protection time delay | instantaneous |
| Net weight | 136 g |
| Connections - terminals | tunnel type terminal (bottom) - 1...6 mm² - flexible, tunnel type terminal (bottom) - 1...10 mm² - rigid, tunnel type terminal (top) - 1...10 mm² - flexible, tunnel type terminal (top) - 1...16 mm² - rigid |
| Comb busbar and distribution block compatibility | YES |
| Limitation class | 3 |
| 9 mm pitches | 2 |
| Temperature derating table | 70 °C ( 21.5 A ) , 65 °C ( 22 A ) , 60 °C ( 22.4 A ) , 55 °C ( 22.9 A ) , 50 °C ( 23.3 A ) , 45 °C ( 23.7 A ) , 40 °C ( 24.2 A ) , 35 °C ( 24.6 A ) , 30 °C ( 25 A ) , 25 °C ( 25.4 A ) , 20 °C ( 25.8 A ) , 15 °C ( 26.2 A ) , 10 °C ( 26.6 A ) , 5 °C ( 27 A ) , 0 °C ( 27.3 A ) , -5 °C ( 27.7 A ) , -10 °C ( 28.1 A ) , -15 °C ( 28.4 A ) , -20 °C ( 28.8 A ) , -25 °C ( 29.2 A ) |
| Height | 93 mm |
| Environment | |
| Quality labels | RCM |
| Overvoltage category | III |
| Pollution degree | 2 |
| IP degree of protection | IP20 |
| Standards | AS/NZS 61009.1, EN/IEC 61009-1, IEC 61009-2-2 |
| Ambient air temperature for operation | -25-70 °C |