| Attribute name | Attribute value |
|---|---|
| Main | |
| Device short name | iID |
| Device application | Electrical Vehicle charger |
| Range | Acti9 |
| Earth-leakage protection class | type B-EV (Electric Vehicle) |
| Neutral position | left |
| Poles description | 4P |
| Quality labels | KEMA, IMQ, NF, VDE |
| Earth-leakage protection time delay | instantaneous |
| Product name | Acti9 iID |
| Product or component type | residual current circuit breaker (RCCB) |
| Earth-leakage sensitivity | 30 mA |
| Network type | AC |
| [In] rated current | 40 A |
| Complementary | |
| Tightening torque | 3.5-3.5 N.m top or bottom |
| Colour | white |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Connection pitch | 18 mm |
| Mechanical durability | 20000 cycles |
| Rated breaking and making capacity | Im 1500 A, Idm 1500 A |
| Power losses per pole | 1.8 W |
| Electrical durability | 15000 cycles |
| Mounting mode | clip-on |
| Residual current tripping technology | voltage independent |
| Power dissipation per pole | 1.5 W |
| Control type | toggle |
| Wire stripping length | 14 mm for top or bottom connection |
| Comb busbar and distribution block compatibility | top or bottom: tooth |
| Connections - terminals | double terminal back 1-16 mm² flexible with ferrule, double terminal back 1-16 mm² flexible, double terminal back 1-25 mm² rigid, double terminal front 1-25 mm² flexible with ferrule, double terminal front 1-25 mm² flexible, double terminal front 1-35 mm² rigid |
| Locking options description | padlocking device |
| Height | 88 mm |
| [Ue] rated operational voltage | 400 V AC 50 Hz |
| Rated conditional short-circuit current | 10 kA |
| Depth | 79 mm |
| Width | 72 mm |
| Local signalling | ON/OFF indication, trip indicator |
| Heat dissipation | 6 W |
| [Ui] rated insulation voltage | 500 V |
| Net weight | 415 g |
| 9 mm pitches | 8 |
| Device location in system | group incomer, outgoer |
| Mounting support | DIN rail |
| Contact position indicator | yes |
| Total power losses | 5.4 W |
| Network frequency | 50 Hz |
| Environment | |
| Ambient air temperature for storage | -40-85 °C |
| Pollution degree | 3 |
| IP degree of protection | IP40 (modular enclosure) conforming to IEC 60529, IP20 conforming to IEC 60529 |
| Electromagnetic compatibility | 8/20 µs impulse withstand, 3 kA conforming to EN/IEC 61008-1 |
| Product certifications | KC, CCC |
| Standards | EN 61008-2-1, IEC/EN 62423, IEC 61008-2-1 |
| Ambient air temperature for operation | -25-60 °C |
| IK degree of protection | IK05 |
| Operating altitude | 0...2000 m |
| Overvoltage category | IV |