| Attribute name | Attribute value |
|---|---|
| Main | |
| Product or component type | analogue output module |
| Range of product | Modicon Quantum automation platform |
| Complementary | |
| Isolation between channels and bus | 1780 V for 1 minute AC |
| Update time | 5 ms |
| Module format | standard |
| Local signalling | 8 LEDs (red) for channel fault, 8 LEDs (green) for channel is turned on, 1 LED (red) for external fault, 1 LED (green) for bus communication is present (Active) |
| Addressing requirement | 8 output words |
| Absolute accuracy error | +/- 0.2 % of full scale at 25 °C |
| Bus current requirement | 550 mA |
| Analogue output number | 8 |
| Maximum power dissipation in W | 5 W |
| External power requirement | 6...30 V |
| Analogue output range | 4...20 mA 0...4095 counts, 4...20 mA 0...16000 counts, 0...25 mA 0...25000 counts, 0...20 mA 0...20000 counts |
| Net weight | 0.3 kg |
| Accuracy drift according to temperature | 0.007 % of full scale/°C maximum, 0.004 % of full scale/°C typical |
| Marking | CE |
| Linearity | +/- 4 µA 4...20 mA 0...16000 counts, +/- 4 µA 0...25 mA 0...25000 counts, +/- 4 µA 0...20 mA 0...20000 counts, +/- 12 µA 4...20 mA 0...4095 counts |
| Loop voltage | 6-30 V DC |
| Setting time | 1.6 ms to 5% of the final value, 3.2 ms to +/-0.1% of the final value |
| Maximum voltage drop | <30 V 25 mA |
| Fault type | open circuit 4...20 mA |
| Environment | |
| Operating altitude | <= 5000 m |
| Relative humidity | 95-95 % without condensation |
| Ambient air temperature for storage | -40-85 °C |
| Standards | CSA C22.2 No 142, UL 508 |
| Resistance to electromagnetic fields | 10 V/m 80-2000 MHz conforming to IEC 801-3 |
| Ambient air temperature for operation | 0-60 °C |
| Product certifications | FM Class 1 Division 2, cUL |