Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| Device short name | XPSMCM |
| Function of module | counter functions, safety time delays, muting function of light curtains conforming to IEC 61800-5-2, switch monitoring conforming to IEC 61800-5-2, safety mat monitoring conforming to IEC 61326-1, two-hand control conforming to EN/ISO 14119, switch monitoring conforming to EN 574, light curtain monitoring conforming to EN/ISO 14119, foot switch monitoring conforming to IEC 60947-5-1, light curtain monitoring conforming to IEC 61496-1, enabling switch monitoring conforming to IEC 60947-5-1, guard monitoring conforming to EN/ISO 14119, emergency stop conforming to ISO 13850 |
| Discrete output current | 400 mA |
| Electrical connection | spring terminal |
| Kit composition | 1 backplane expansion connector, 1 safety controller CPU |
| [Us] rated supply voltage | 24 V - 20...20 % DC |
| Number of inputs | 2 digital for interlock start/restart or external device monitoring, 8 digital for input connection |
| Discrete input current | 400 mA |
| Product or component type | modular safety controller CPU kit |
| Number of outputs | 2 configurable for diagnostic connection, 4 test for line control outputs, 2 safety outputs OSSD for contactor/drive connection |
| Discrete input voltage | 24 V |
| Range of product | Modicon Safety automation |
| Discrete input type | safety input, PNP |
| Discrete output type | PNP |
| Complementary | |
| Safety level | SILCL 3 conforming to IEC 62061, type 4 conforming to IEC 61496-1, can reach PL = e conforming to ISO 13849-1, can reach category 4 conforming to ISO 13849-1 |
| Data storage equipment | SD card (optional) |
| Synchronisation time between inputs | < 0.5 ms |
| Depth | 114.5 mm |
| Inductive load | 30 mH |
| Width | 22.5 mm |
| Load capacitance | 0.82 µF |
| Mounting support | omega 35 mm DIN rail conforming to EN 50022 |
| Quality labels | CE |
| Power dissipation in W | 3 W |
| Net weight | 0.26 kg |
| Maximum number of I/O expansion module | 14 with 16 discrete output(s) for output, 14 with 128 discrete output(s) for input |
| Local signalling | 2 LEDs yellow with STATUS marking for output channel, 2 LEDs yellow with RST marking for restart signal, 2 LEDs green/red with OUT marking for output status, 8 LEDs yellow with IN marking for input status, 1 LED blue with EN marking for master enable, 1 LED orange with COM marking for communication, 1 LED red with E EX marking for external error, 1 LED red with E IN marking for internal error, 1 LED green with RUN marking for RUN (status), 1 LED green with PWR marking for power ON |
| Cable cross section | 0.5-1 mm² - AWG 20...AWG 18 flexible cablewith cable end, with double bezel, 0.25-2.5 mm² - AWG 23...AWG 14 solid cablewithout cable end, 0.25-2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, without bezel, 0.2-2.5 mm² - AWG 24...AWG 14 solid cablewithout cable end, 0.25-2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, with bezel, 0.2-2.5 mm² - AWG 24...AWG 14 flexible cablewithout cable end |
| Integrated connection type | USB 2.0 port, backplane expansion bus |
| Height | 99 mm |
| Connections - terminals | 2 spring terminals, removable terminal block, 1 spring terminals, removable terminal block |
| Environment | |
| Insulation | 250 V AC between power supply and housing conforming to IEC 61800-5-1 |
| Overvoltage category | II |
| Safety reliability data | MTTFd < 100 years high, DC > 99 %, PFHd = 6.06E-9 1/h |
| Service life | 20 year(s) |
| Ambient air temperature for storage | -20-85 °C |
| Relative humidity | 10-95 % |
| IP degree of protection | IP20 |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to IEC 61800-5-1 |
| Vibration resistance | +/-0.35 mm (f= 10-55 Hz) conforming to IEC 61496-1 |
| Shock resistance | 10 gn (duration = 16 ms) for 1000 shocks on each axis conforming to IEC 61496-1 |
| Electromagnetic compatibility | susceptibility to electromagnetic fields - test level: 30 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3, susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to IEC 61000-4-3, electrostatic discharge immunity test - test level: 20 kV (on air) conforming to IEC 61000-4-2, electrostatic discharge immunity test - test level: 6 kV (on contact) conforming to IEC 61000-4-2 |
| Pollution degree | 2 |
| Standards | IEC 62061, IEC 61800-5-1, IEC 61508, ISO 13849-1, IEC 61496-1 |
| Ambient air temperature for operation | -10-55 °C |
| Product certifications | cULus, RCM, TÜV |