| Attribute name | Attribute value |
|---|---|
| Main | |
| Device application | distribution |
| Suitability for isolation | yes conforming to EN/IEC 60947-2 |
| Standards | EN/IEC 60947-2 |
| Number of protected poles | 2 |
| Trip unit technology | thermal-magnetic |
| Network type | DC, AC |
| Device short name | C60N |
| Breaking capacity | 6 kA Icu at 440 V AC 50/60 Hz between phases conforming to EN/IEC 60947-2, 20 kA Icu at 240 V AC 50/60 Hz between phases conforming to EN/IEC 60947-2, 10 kA Icu at 415 V AC 50/60 Hz between phases conforming to EN/IEC 60947-2, 20 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 |
| Range | Multi9 |
| Product certifications | CCC, KC, EAC |
| Curve code | C |
| Range of product | Multi9 |
| Poles description | 2P |
| Utilisation category | category A conforming to EN/IEC 60947-2 |
| Product name | Multi9 C60 |
| Product or component type | miniature circuit-breaker |
| Breaking capacity code | N |
| [In] rated current | 10 A at 50 °C conforming to EN/IEC 60947-2 |
| Complementary | |
| Provision for padlocking | padlockable |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 |
| Electrical durability | 10000 cycles |
| Earth-leakage protection | separate block |
| Height | 81 mm |
| [Ics] rated service breaking capacity | 20 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC, 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz, 16 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz, 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz |
| Magnetic tripping limit | 12 x In +/- 20 % DC, 8.5 x In +/- 20 % AC |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Net weight | 0.24 kg |
| 9 mm pitches | 4 |
| Tightening torque | 2-2 N.m top or bottom |
| Colour | grey |
| Connection pitch | 18 mm between phases |
| Mechanical durability | 20000 cycles |
| Mounting mode | clip-on |
| Control type | toggle |
| Wire stripping length | 14 mm for top or bottom connection |
| [Ue] rated operational voltage | <= 125 V DC, 440 V AC 50/60 Hz between phases, 415 V AC 50/60 Hz between phases, 240 V AC 50/60 Hz between phases |
| Depth | 72 mm |
| Width | 36 mm |
| Local signalling | ON/OFF indication |
| Connections - terminals | tunnel type terminal (top or bottom)1-25 mm² - flexible with ferrule, tunnel type terminal (top or bottom)1-25 mm² - flexible, tunnel type terminal (top or bottom)1-25 mm² - rigid |
| Limitation class | 3 |
| Mounting support | DIN rail |
| Contact position indicator | yes |
| Network frequency | 50/60 Hz |
| Environment | |
| Relative humidity | 95-95 % at 55-55 °C |
| Ambient air temperature for storage | -40-80 °C |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Ambient air temperature for operation | -30-70 °C |
| Overvoltage category | IV |
| Heat dissipation | 3.6-3.6 W at 415 V - 10 A |
| Pollution degree | 3 conforming to EN/IEC 60947-2 |
| IP degree of protection | IP40 (modular enclosure) conforming to IEC 60529, IP20 conforming to IEC 60529 |