| Attribute name | Attribute value |
|---|---|
| Main | |
| [Ue] rated operational voltage | 240 V |
| Poles description | 2P |
| Range | MAX9 |
| Product or component type | residual current circuit breaker (RCCB) |
| Earth-leakage sensitivity | 30 mA |
| Network type | AC |
| [In] rated current | 40 A conforming to AS/NZS 61008.1 |
| Network frequency | 50 Hz |
| Complementary | |
| Rated conditional short-circuit current | MAX9 MCB: Inc 6 kA 40 A |
| Tightening torque | 3.5-3.5 N.m top or bottom |
| Depth | 75 mm |
| Width | 36 mm |
| Colour | white (RAL 9003) |
| [Uimp] rated impulse withstand voltage | 4 kV |
| Local signalling | ON/OFF indication |
| Mechanical durability | 10000 cycles |
| Grid distance | 35 mm |
| Rated breaking and making capacity | Im 500 A at 240 V AC 50 Hz conforming to AS/NZS 61008.1 |
| Quality labels | RCM |
| Electrical durability | 4000 cycles AC 50 Hz |
| Mounting mode | clip-on |
| [Ui] rated insulation voltage | 440 V AC 50 Hz conforming to AS/NZS 61008.1 |
| Earth-leakage protection time delay | instantaneous |
| Control type | toggle |
| Wire stripping length | 14 mm for top or bottom connection |
| Net weight | 210 g |
| Surge current | 250 A |
| Connections - terminals | tunnel type terminals (top or bottom) |
| Earth-leakage protection class | type A |
| 9 mm pitches | 4 |
| Temperature derating table | 70 °C ( 25 A ) , 65 °C ( 27.5 A ) , 60 °C ( 30 A ) , 55 °C ( 32.5 A ) , 50 °C ( 35 A ) , 45 °C ( 37.5 A ) , 40 °C ( 40 A ) |
| Mounting support | DIN rail |
| Standards | EN/IEC 61008-1, IEC 61008-2-1 |
| Height | 85 mm |
| Environment | |
| Overvoltage category | III |
| Relative humidity | 95-95 % at 55-55 °C |
| Ambient air temperature for storage | -40-85 °C |
| Pollution degree | 2 |
| IP degree of protection | IP20 |
| Ambient air temperature for operation | -25-70 °C |