Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| Circuit breaker application | distribution |
| Device short name | iC60H3 RCBO |
| Breaking capacity | 10000 A Icn at 400/415 V |
| Range | Acti9 |
| Earthing system | TN |
| Curve code | C |
| Poles description | 3P + Ns |
| Product name | Acti9 iC60 RCBO |
| Product or component type | residual current breaker with overcurrent protection (RCBO) |
| Earth-leakage sensitivity | 30 mA |
| [In] rated current | 50 A at 30 °C |
| Complementary | |
| Provision for padlocking | lead seal, padlockable with padlock Ø 4 mm |
| [Uimp] rated impulse withstand voltage | 4 kV |
| Grid distance | 45 mm |
| Suitability for isolation | yes conforming to IEC 61009-1 |
| Electrical durability | 5000 cycles |
| Connections - terminals | screw clamp terminal (top) 1-16 mm² flexible, screw clamp terminal (top) 1-25 mm² rigid without cable end |
| Comb busbar and distribution block compatibility | YES |
| Earth-leakage protection class | type A |
| Locking options description | ON/OFF locking facilities |
| Earth-leakage protection | integrated |
| Number of protected poles | 3 |
| Test button operating voltage | 260-457 V |
| Residual current tripping technology | voltage dependent |
| Height | 112 mm |
| [Ics] rated service breaking capacity | 7500 A |
| Trip unit technology | thermal-magnetic |
| Neutral position | left |
| [Ui] rated insulation voltage | 500 V |
| Earth-leakage protection time delay | instantaneous |
| Net weight | 462 g |
| Surge current | 250 A |
| 9 mm pitches | 6 |
| Device location in system | outgoer |
| Network type | AC |
| Tightening torque | power circuit: 2.5-2.5 N.m bottom, power circuit: 2.5-2.5 N.m top |
| Colour | white |
| Mechanical durability | 20000 cycles |
| Mounting mode | clip-on |
| Control type | toggle |
| Wire stripping length | power circuit: 14 mm for top connection, power circuit: 11 mm for bottom connection |
| [Icw] rated short-time withstand current | Icw: 250 A during 8/20 µs impulse withstand |
| [Ue] rated operational voltage | 400/415 V |
| Depth | 77.2 mm |
| Width | 54 mm |
| Local signalling | ON/OFF indication |
| Limitation class | 3 |
| Mounting support | chassis, DIN rail |
| Network frequency | 50/60 Hz |
| Operating voltage earthleakage protection | 150-457 V |
| Environment | |
| Relative humidity | 95-95 % at 55-55 °C |
| Ambient air temperature for storage | -25-70 °C |
| Tropicalisation | 2 |
| IP degree of protection | IP20 |
| Ambient air temperature for operation | -5-60 °C |
| Standards | IEC 61009-2-2, IEC 61009-1, AS/NZS 61009.1 |