| Attribute name | Attribute value |
|---|---|
| Main | |
| Product or component type | analogue input module |
| Type of filter | single pole low pass - 3 dB at 34 Hz +/- 25 % |
| Range of product | Modicon Quantum automation platform |
| Complementary | |
| Isolation between channels and bus | 1780 V AC for 60 s |
| Module format | standard |
| Common mode rejection | > - 90 dB 60 Hz |
| Linearity error | +/- 6 µA max 4...20 mA, +/- 6 µA max 0...25 mA, +/- 6 µA max 0...20 mA, +/- 12 µA max 4...20 mA |
| Absolute maximum input | 30 mA |
| Local signalling | 16 LEDs (red) for channel fault, 16 LEDs (green) for channel is turned on, 1 LED (red) for external fault, 1 LED (green) for bus communication is present (Active) |
| Absolute accuracy error | +/- 0.125 % of full scale |
| Addressing requirement | 17 input words |
| Bus current requirement | 360 mA |
| Power dissipation in W | 5 W |
| Update time | 15 ms 2 wires/4 wires |
| Analogue input number | 16 |
| Input type | differential |
| Net weight | 0.3 kg |
| Accuracy drift according to temperature | <= 0.0050 % of full scale /°C, +/- 0.0025 % of full scale/°C |
| Analogue input resolution | 0...4095 counts 4...20 mA, 0...25000 counts 0...25 mA, 0...20000 counts 0...20 mA, 0...16000 counts 4...20 mA |
| Marking | CE |
| Fault type | broken wire 4...20 mA |
| Input impedance | 250 Ohm |
| Environment | |
| Operating altitude | <= 5000 m |
| Resistance to electrostatic discharge | 8 kV on air conforming to IEC 801-2, 4 kV contact conforming to IEC 801-2 |
| Relative humidity | 95-95 % without condensation |
| Ambient air temperature for storage | -40-85 °C |
| Standards | CSA C22.2 No 142, UL 508 |
| Resistance to electromagnetic fields | 10 V/m 80-1000 MHz conforming to IEC 801-3 |
| Ambient air temperature for operation | 0-60 °C |
| Product certifications | cUL, FM Class 1 Division 2 |