Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| Contact operation | slow-break |
| Sale per indivisible quantity | 1 |
| Fixing collar material | zamak |
| Type of operator | spring return |
| [Us] rated supply voltage | 24 V AC/DC at 50/60 Hz |
| Contacts type and composition | 1 NO + 1 NC |
| Connections - terminals | screw clamp terminals, 1 x 0.22...2 x 2.5 mm² without cable end conforming to IEC 60947-1, screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to IEC 60947-1 |
| Light source | universal LED |
| Device short name | XB4F |
| Head type | built-in-flush |
| Range of product | Harmony XB4 |
| Bulb base | integral LED |
| Operator profile | green flush |
| Bezel material | chromium plated metal |
| Shape of signaling unit head | round |
| Product or component type | illuminated push-button |
| Mounting diameter | 30.5 mm |
| Operator additional information | with plain lens |
| Complementary | |
| Device mounting | built-in |
| Shape of screw head | slotted compatible with flat Ø 5.5 mm screwdriver, slotted compatible with flat Ø 4 mm screwdriver, cross compatible with pozidriv No 1 screwdriver, cross compatible with Philips no 1 screwdriver |
| Electrical reliability | λ < 10exp(-8) at 17 V and 5 mA in clean environment conforming to IEC 60947-5-4, λ < 10exp(-6) at 5 V and 1 mA in clean environment conforming to IEC 60947-5-4 |
| Compatibility code | XB4 |
| [Ie] rated operational current | 1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1, 0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1, 0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1, 0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1, 6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1, 3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1 |
| Surge withstand | 1 kV conforming to IEC 61000-4-5 |
| Electrical durability | 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C, 1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C, 1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C, 1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C, 1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C |
| Device presentation | complete product |
| Customizable | 1, no |
| Cap/operator or lens colour | green |
| Fixing mode | by screws recommended torque: 0.8 N.m |
| Operating force | 3.8 N, 3.5 N NC changing electrical state |
| Height | 47 mm |
| [Us] rated supply voltage | 24 V |
| [Ui] rated insulation voltage | 600 V (pollution degree 3) conforming to IEC 60947-1 |
| Resistance to high pressure washer | 7000000 Pa at 55 °C, distance : 0.1 m |
| Current consumption | 18 mA |
| Net weight | 0.132 kg |
| [Ith] conventional free air thermal current | 10 A conforming to IEC 60947-5-1 |
| Positive opening | with conforming to IEC 60947-5-1 appendix K |
| Tightening torque | 0.8-1.2 N.m conforming to IEC 60947-1 |
| Mechanical durability | 10000000 cycles |
| Supply voltage limits | 21.6-26.4 V AC, 19.2-30 V DC |
| Contacts material | silver alloy (Ag/Ni) |
| Operating travel | 4.3 mm (total travel), 2.6 mm (NO changing electrical state), 1.5 mm (NC changing electrical state) |
| Depth | 55 mm |
| Width | 36.6 mm |
| Signalling type | steady |
| Service life | 100000 h at rated voltage and 25 °C |
| GCR BRIDGE | XB4FWCUST02 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-1 |
| Short-circuit protection | 10 A cartridge fuse type gG conforming to IEC 60947-5-1 |
| Terminals description ISO n°1 | (13-14)NO, (21-22)NC |
| Contacts usage | standard contacts |
| Environment | |
| Resistance to fast transients | 2 kV conforming to IEC 61000-4-4 |
| Resistance to electrostatic discharge | 8 kV in free air (in insulating parts) conforming to IEC 61000-4-2, 6 kV on contact (on metal parts) conforming to IEC 61000-4-2 |
| Ambient air temperature for storage | -40-70 °C |
| Product certifications | EAC, CCC, CSA, UL listed |
| Protective treatment | TH |
| IP degree of protection | Type 4X conforming to UL 50 E, Type 4 conforming to UL 50 E, Type 12 conforming to UL 50 E, Type 13 conforming to UL 50 E, IP69K conforming to ISO 20653, IP69 conforming to IEC 60529, IP67 conforming to IEC 60529, IP66 conforming to IEC 60529 |
| Resistance to electromagnetic fields | 10 V/m conforming to IEC 61000-4-3 |
| Ambient air temperature for operation | -40-70 °C |
| IK degree of protection | IK06 conforming to IEC 50102 |
| Electromagnetic emission | class B conforming to IEC 55011 |
| Electrical shock protection class | class I conforming to IEC 60536 |
| Vibration resistance | 2 mm peak to peak (f= 2-10 Hz) conforming to IEC 60068-2-6, 5 gn (f= 10-500 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 25 gn (duration = 6 ms) for 1000 shocks on each axis conforming to IEC 60068-2-27, 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27, 30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27 |
| Standards | JIS C8201-1, CE, JIS C8201-5-1, IEC 60947-1, UL 508, IEC 60947-5-4, IEC 60947-5-1, CSA C22.2 No 14 |