| Attribute name | Attribute value |
|---|---|
| Main | |
| Range of product | Pro-face STW6000 |
| Product or component type | touch panel screen |
| Complementary | |
| Display type | colour TFT LCD |
| Display colour | 16 million colours |
| Display size | 15 inch |
| Type of cooling | AN (air natural) |
| Input voltage limits | 19.2...28.8 V DC |
| Backlight lifespan | 50000 hours with white |
| Electrical connection | cable 2 mm², AWG 14, max resistance 100 Ohm for functional grounding |
| Height | 268 mm |
| Maximum power consumption in W | 5.9 W when backlight is OFF, 15 W when power is not supplied to external devices, 18.4 W |
| Depth | 50 mm |
| Width | 412 mm |
| Integrated connection type | 2 Ethernet TCP/IP female RJ45 10BASE-T/100BASE-TX, USB 2.0 type A |
| Touch panel | single touch analogue resistive |
| Rated short-duration power frequency withstand voltage | 1000 V AC during 1 min |
| Net weight | 2.7 kg |
| Display resolution | 1366 x 768 pixels FWXGA |
| Cut-out dimensions | 394 x 250 mm |
| Inrush current | 30 A |
| Brightness | 16 levels via touch panel |
| [Us] rated supply voltage | 24 V DC |
| Maximum cycle time | 10 ms |
| Environment | |
| Environmental characteristic | corrosive gas free |
| Ambient air temperature for storage | -20-60 °C |
| Directives | 2014/35/EU - low voltage directive, 2014/30/EU - electromagnetic compatibility |
| IP degree of protection | IP65f (front panel) conforming to IEC 61131-2 |
| Electromagnetic compatibility | electrostatic discharge immunity test - test level: 8 kV level 3 (air discharge) conforming to EN/IEC 61000-4-2, electrostatic discharge immunity test - test level: 6 kV level 3 (contact discharge) conforming to EN/IEC 61000-4-2, electrical fast transient/burst immunity test - test level: 1 kV (signal ports) conforming to IEC 61000-4-4, electrical fast transient/burst immunity test - test level: 2 kV (power ports) conforming to IEC 61000-4-4 |
| Pollution degree | 2 |
| Ambient air temperature for operation | 0-50 °C |
| Operating altitude | 2000 m |
| NEMA degree of protection | NEMA 13 front panel (in enclosure), NEMA Type 1, NEMA 4X front panel (indoor use) |
| Vibration resistance | 9.8 m/s² (f = 9-150 Hz), 3.5 mm (f = 5-9 Hz) X, Y, Z directions for 10 cycles (approx. 100 min) conforming to EN/IEC 61131-2 |
| Shock resistance | 147 m/s² (X, Y, Z directions for 3 times) conforming to EN/IEC 61131-2 |
| Insulation resistance | >= 10 MOhm |
| Standards | KN 61000-6-2, KN 11, CSA C22.2 No 61010-2-201, UL 61010-2-201, EN 61131-2, EN 61000-6-2, EN 61000-6-4 |
| Product certifications | UKCA, RCM, IC, UL/cUL listed, EAC, CE |