Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| Device short name | C60H-DC |
| Device application | distribution |
| Suitability for isolation | yes conforming to EN/IEC 60947-2 |
| Breaking capacity | 5 kA AIR at 12...500 V DC conforming to UL 1077, 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2, 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2, 20 kA Icu at 220 V DC conforming to EN/IEC 60947-2, 6 kA Icu at 500 V DC conforming to GB 14048.2, 10 kA Icu at 440 V DC conforming to GB 14048.2, 20 kA Icu at 220 V DC conforming to GB 14048.2 |
| Range | Multi9 |
| Number of protected poles | 2 |
| Curve code | C |
| Range of product | C60 |
| Trip unit technology | thermal-magnetic |
| Poles description | 2P |
| Utilisation category | category A conforming to EN/IEC 60947-2 |
| Product name | Multi9 C60H-DC |
| Product or component type | miniature circuit-breaker |
| Breaking capacity code | H |
| Network type | DC |
| [In] rated current | 30 A at 25 °C |
| Complementary | |
| Product compatibility | C60 accessories, C60 auxiliary |
| Tightening torque | 3.5-3.5 N.m top or bottom |
| Provision for padlocking | padlockable |
| Colour | grey |
| Connection pitch | 18 mm between phases |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 |
| Compatibility code | C60H-DC |
| Mechanical durability | 20000 cycles |
| Electrical durability | 3000 cycles L/R = 2 ms |
| Mounting mode | clip-on |
| Control type | toggle |
| Wire stripping length | 14 mm for top or bottom connection |
| Comb busbar and distribution block compatibility | top or bottom: standard |
| Locking options description | in position O |
| Earth-leakage protection | without |
| Height | 81 mm |
| [Ics] rated service breaking capacity | 4.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V DC, 7.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V DC, 15 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC, 15 kA 75 % conforming to GB 14048.2 - 220 V DC, 7.5 kA 75 % conforming to GB 14048.2 - 440 V DC, 4.5 kA 75 % conforming to GB 14048.2 - 500 V DC |
| [Ue] rated operational voltage | 12...500 V DC |
| Magnetic tripping limit | 8.5 x In +/- 20 % AC |
| Depth | 73 mm |
| Width | 36 mm |
| Local signalling | ON/OFF indication |
| [Ui] rated insulation voltage | 500 V DC conforming to EN/IEC 60947-2 |
| Connections - terminals | tunnel type terminal (top or bottom) - 3 cable(s) 4-4 mm² (AWG 6) - flexible stranded, tunnel type terminal (top or bottom) - 2 cable(s) 1-16 mm² (AWG 18...AWG 6) - flexible with ferrule, tunnel type terminal (top or bottom) - 2 cable(s) 1-16 mm² (AWG 18...AWG 6) - flexible, tunnel type terminal (top or bottom) - 2 cable(s) 1-16 mm² (AWG 18...AWG 6) - rigid stranded, tunnel type terminal (top or bottom)1-25 mm² (AWG 18...AWG 4) - flexible with ferrule, tunnel type terminal (top or bottom)1-25 mm² (AWG 18...AWG 4) - flexible, tunnel type terminal (top or bottom)1-35 mm² (AWG 18...AWG 2) - rigid stranded |
| Net weight | 0.256 kg |
| Limitation class | 3 conforming to EN/IEC 60947-2 |
| 9 mm pitches | 4 |
| Mounting support | DIN rail |
| Contact position indicator | yes |
| Environment | |
| Relative humidity | 95-95 % at 55-55 °C |
| Ambient air temperature for storage | -40-85 °C |
| Pollution degree | 3 conforming to EN/IEC 60947-2 |
| IP degree of protection | IP40 (modular enclosure) conforming to IEC 60529, IP20 conforming to IEC 60529 |
| Product certifications | IEC, CCC, UR |
| Standards | EN/IEC 60947-2, GB 14048.2, UL 1077 |
| Tropicalisation | 2 conforming to GB 14048.2, 2 conforming to IEC 60068-2 |
| Ambient air temperature for operation | -25-70 °C |
| Operating altitude | 2000 m |
| Overvoltage category | IV |