| Attribute name | Attribute value |
|---|---|
| Main | |
| Mechanical durability | 5 Mcycles |
| Device short name | LX1G |
| Product compatibility | LC1G400...500 |
| Operating time | 40...55 ms closing, 20...35 ms opening |
| Poles description | 4P |
| Number of modules per PLC per PC | 1 |
| Maximum operating rate | 600 cyc/mn 60 °C |
| Range | TeSys |
| Product or component type | contactor coil |
| Range compatibility | TeSys G LX1G contactor coil |
| Range of product | TeSys G |
| [Uc] control circuit voltage | 200...500 V AC/DC 50/60 Hz |
| Complementary | |
| Inrush power in W | 260.0 W DC |
| Hold-in power consumption in VA | 14.9-14.9 VA at 480 V AC, 60 Hz |
| Coil technology | built-in bidirectional peak limiting |
| Connections - terminals | control circuit: push-in termination 2 cable(s) 0.5-1.0 mm² rigid or stranded with cable end sleeve AWG 20...AWG 18, control circuit: push-in termination 1 cable(s) 0.25-2.5 mm² flexible with cable end sleeve AWG 24...AWG 14, control circuit: push-in termination 1 cable(s) 0.2-2.5 mm² solid stranded without cable end sleeve AWG 26...AWG 12 |
| Inrush power in VA | 400-400 VA at 480 V AC, 60 Hz |
| Hold-in power consumption in W | 4.8-4.8 W for DC network |
| Control circuit voltage limits | drop-out: 0...0.45 Uc (at 60 °C), operational: 0.8...1.1 Uc (at 60 °C) |
| Environment | |
| Permissible ambient air temperature around the device | -40-70 °C at Uc |
| Depth | 93.0 mm |
| Width | 185.0 mm |
| Quantity per set | 1 |
| Operating altitude | 5000 m with derating factor, 3000 m without derating |
| Ambient air temperature for storage | -60-80 °C |
| Pollution degree | 3 conforming to IEC 60947-1 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Electromagnetic compatibility | voltage dips and interruptions immunity test conforming to SEMI F47, immunity to radiated radio-electrical interference - test level: 20 V/m conforming to EN/IEC 61000-4-3, emission tests criteria A conforming to IEC 60947-4-1, EMC immunity conforming to IEC 60947-4-1 |
| Standards | CSA C22.2 No 60947-4-1, UL 60947-4-1A, EN/IEC 60947-4-1 |
| Ambient air temperature for operation | -25-60 °C |
| Height | 167.0 mm |