| Attribute name | Attribute value |
|---|---|
| Main | |
| Device short name | LTMR |
| Device application | equipment monitoring and control |
| Supply voltage limits | 93.5-264 V AC |
| Bus type | Modbus 2-wire RS 485 interface, addressing 1...247, transmission rate 1.2...19.2 kbit/s, terminal block with 2 shielded twisted pairs, Modbus 2-wire RS 485 interface, addressing 1...247, transmission rate 1.2...19.2 kbit/s, RJ45 with 2 shielded twisted pairs |
| [Us] rated supply voltage | 100...240 V AC 50/60 Hz |
| Range | TeSys |
| Communication port protocol | Modbus |
| Current consumption | 8...62.8 mA |
| Measurement current | 1.35-27 A |
| Product name | TeSys T |
| Product or component type | motor controller |
| Complementary | |
| Metering type | imbalance current, earth-fault current, average current Iavg, phase current I1, I2, I3 RMS, temperature |
| Tightening torque | control circuit: 0.5-0.6 N.m flat screwdriver 3 mm |
| Load current | 5 A at 30 V DC for logic output, 5 A at 250 V AC for logic output |
| Web services | web server |
| Protection type | thermal overload protection, locked rotor, thermal protection, power factor variation, phase failure, load fluctuation, overload, phase unbalance, earth-leakage protection, overload (long time), reverse polarity protection |
| Compatibility code | LTMR |
| Current state 0 guaranteed | logic input: 0...40 V and <= 15 mA for 25 ms |
| Measurement accuracy | 5 % active and reactive power, 1 % current, 0,02 temperature, +/- 30 min/year internal clock, 5 % earth fault current external measurement, 3 % power factor, 1 % voltage (100...830 V), 5...15 % earth fault current internal measurement |
| Electromagnetic compatibility | control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5, temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5, temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5, conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6, voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11, fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4, fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4, radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3, control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5, relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5, relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5, communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5, electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 |
| Associated fuse rating | 0.5 A gG for control circuit, 4 A gG for output |
| Input current | 7.5 mA at 240 V, 3.1 mA at 100 V |
| Connections - terminals | control circuit: connector 2 cable(s) 0.2-1 mm² (AWG 24...AWG 14) solid without cable end, control circuit: connector 2 cable(s) 0.5-1.5 mm² (AWG 24...AWG 14) flexible without cable end, control circuit: connector 2 cable(s) 0.2-1.5 mm² (AWG 24...AWG 14) flexible without cable end, control circuit: connector 2 cable(s) 0.2-1 mm² (AWG 24...AWG 14) flexible with cable end, control circuit: connector 1 cable(s) 0.2-2.5 mm² (AWG 24...AWG 14) solid without cable end, control circuit: connector 1 cable(s) 0.25-2.5 mm² (AWG 24...AWG 14) flexible without cable end, control circuit: connector 1 cable(s) 0.2-2.5 mm² (AWG 24...AWG 14) flexible without cable end, control circuit: connector 1 cable(s) 0.25-2.5 mm² (AWG 24...AWG 14) flexible with cable end |
| Maximum operating rate | 1800 cyc/h |
| Logic input number | 6 |
| Pollution degree | 3 |
| Permissible power | 30 W (DC-13), Ie = 1.25 A, 500000 cycles (output), 480 VA (AC-15), Ie = 2 A, 500000 cycles (output) |
| Connection pitch | 5.08 mm |
| Height | 61 mm |
| Contacts type and composition | 3 NO, 1 NO + 1 NC fault signal |
| Maximum operating frequency | 2 Hz |
| Depth | 122.5 mm |
| Overvoltage category | III |
| Width | 91 mm |
| Short-circuit withstand | 100 kA conforming to EN/IEC 60947-4-1 |
| [Ui] rated insulation voltage | 690 V conforming to UL 508, 690 V conforming to CSA C22.2 No 14, 690 V conforming to EN/IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | 0.8 kV communication circuit conforming to EN/IEC 60947-4-1, 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1, 4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1 |
| Net weight | 0.53 kg |
| Current state 1 guaranteed | logic input: 79...264 V and >= 2 mA for 25 ms |
| Network and machine diagnosis type | trip context information, phase fault and earth fault trip counters, running hours counter/operating time, trip history information, event recording, motor control command recording, waiting time after overload tripping, remaining operating time before overload tripping, starting current and time, fault recording |
| Environment | |
| IP degree of protection | IP20 |
| Fire resistance | 960 °C conforming to UL 94, 650 °C conforming to EN/IEC 60695-2-12 |
| Protective treatment | TH conforming to EN/IEC 60068, 48 h conforming to EN/IEC 60070-2-11, 12 x 24 hour cycles conforming to EN/IEC 60068-2-30 |
| Ambient air temperature for storage | -40-80 °C |
| Ambient air temperature for operation | -20-60 °C |
| Mechanical robustness | shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27, vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6, vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 |
| Operating altitude | <= 2000 m without derating |
| Standards | IACS E10, IEC 60947-4-1, EN 60947-4-1, UL 508, CSA C22.2 No 14 |
| Product certifications | C-Tick, CSA, BV, ATEX, KERI, DNV, NOM, GL, UL, EAC, CCC, ABS, RINA, LROS (Lloyds register of shipping), RMRoS |