| Attribute name | Attribute value |
|---|---|
| Main | |
| Protective treatment | TC |
| Discrete input number | 16 conforming to IEC 1131-2 Type 1 |
| Discrete input logic | positive |
| Discrete output voltage | 24 V DC, <= 30 V DC |
| Discrete input voltage | 24 V DC |
| Discrete output logic | positive |
| Range of product | Modicon Momentum automation platform |
| Group of channels | 2 groups of 4 outputs, 4 groups of 4 inputs |
| Discrete output type | solid state switch |
| Discrete output number | 8 |
| Product or component type | discrete solid state I/O base DC |
| Complementary | |
| Voltage state 0 guaranteed | -3...5 V |
| Input voltage limits | - 3...30 V |
| Marking | CE |
| Isolation between channels and bus | 500 V AC |
| Fault type | overload on output, short circuit on output |
| Height | 141.5 mm |
| [Us] rated supply voltage | 24 V DC |
| Discrete output current | 8 A per group, 2 A per point, 16 A per module |
| Depth | 47.5 mm |
| Width | 125 mm |
| Peak output current | 2.8 A |
| Input resistance | 4 kOhm |
| Voltage state 1 guaranteed | 11...30 V |
| Maximum leakage current | 1 mA at 24 V (output circuit) |
| Net weight | 0.22 kg |
| Response time | 3.3 ms from state 1 to state 0 on input, 2.2 ms from state 0 to state 1 on input, < 0.1 ms from state 1 to state 0 on output, < 0.1 ms from state 0 to state 1 on output |
| Current state 0 guaranteed | <= 1.2 mA |
| Current state 1 guaranteed | >= 2.5 mA |
| Current consumption | 250 mA at 24 V DC |
| Terminals description PLC n°1 | (9)IN_DIS#9, (3)IN_DIS#3, (2)IN_DIS#2, (8)IN_DIS#8, (10)IN_DIS#10, (12)IN_DIS#12, TB, (5)IN_DIS#5, (13)IN_DIS#13, (14)IN_DIS#14, (6)IN_DIS#6, (4)IN_DIS#4, (1)IN_DIS#1, (16)IN_DIS#16, (15)IN_DIS#15, (7)IN_DIS#7, (L+)PW_POS, (M-)PW_NEG, (11)IN_DIS#11 |
| Terminals description PLC n°2 | TB_1, (2L+)PW_POS, (1L+)PW_POS, (3)OUT_DIS#3, (7)OUT_DIS#7, (8)OUT_DIS#8, (6)OUT_DIS#6, (4)OUT_DIS#4, (2)OUT_DIS#2, (1)OUT_DIS#1, (5)OUT_DIS#5 |
| Power dissipation | <= 10 W, 6.5 W |
| Environment | |
| Resistance to electrostatic discharge | 8 kV on air conforming to IEC 801-2, 4 kV contact conforming to IEC 801-2 |
| Relative humidity | 95-95 % without condensation |
| Ambient air temperature for storage | -40-85 °C |
| Resistance to electromagnetic fields | 10 V/m 80...1000 MHz conforming to IEC 801-3 |
| Ambient air temperature for operation | 0-60 °C |
| Operating altitude | <= 5000 m |
| Product certifications | CSA, UL |