| Attribute name | Attribute value |
|---|---|
| Main | |
| Discrete output number | 8 |
| Product or component type | relay discrete output module |
| Range of product | Modicon Quantum automation platform |
| Complementary | |
| Isolation between channels and bus | 2500 V DC for 1 minute, 1780 Vrms AC for 1 minute |
| Module format | standard |
| Mechanical durability | 10000000 cycles |
| Local signalling | 8 LEDs (green) for input status, 1 LED (red) for external fault detected (F), 1 LED (green) for bus communication is present (Active) |
| Addressing requirement | 0.5 output word |
| Bus current requirement | 560 mA |
| Contacts type and composition | 1 NO/NC |
| Maximum response time on input open | 20 ms at state 1 to state 0, 10 ms at state 0 to state 1 |
| Switching frequency | F = 0.5/I²L inductive load, 30 Hz resistive load |
| Isolation between channels | 2500 V DC, 1780 Vrms AC for 1 minute |
| Net weight | 0.3 kg |
| Surge current | 20 A for 10 ms capacitive |
| Output overvoltage protection | internal by varistor, 275 V |
| Marking | CE |
| Discrete output voltage | 5...30 V DC, 30...150 V DC, 20...250 V AC |
| Contact form | Form C |
| Electrical durability | 50000 cycles 500 mA 30...150 V DC resistive, 200000 cycles 5 A 250 V AC resistive, 100000 cycles 5 A 30 V DC resistive, 100000 cycles 300 mA 30...150 V DC resistive, 100000 cycles 30...150 V DC interposing relay, 100000 cycles 100 mA 30...150 V DC L/R = 10 ms |
| Switching capacity in VA | 1250 VA resistive |
| Maximum load current | 5 A 250/30 V AC/DC resistive at 60 °C, 300 mA 30...50 V DC resistive, 3 A 250/30 V AC/DC, 2 A 250/30 V AC/DC tungsten 1/4 hp cos phi = 0.4 , 100 mA 30...50 V DC L/R = 10 ms |
| Power dissipation | 2.75 W + (0.5 x the number of points on) |
| Environment | |
| Operating altitude | <= 5000 m |
| Resistance to electrostatic discharge | 8 kV on air conforming to IEC 801-2, 4 kV contact conforming to IEC 801-2 |
| Relative humidity | 95-95 % without condensation |
| Ambient air temperature for storage | -40-85 °C |
| Standards | CSA C22.2 No 142, UL 508 |
| Resistance to electromagnetic fields | 10 V/m 80-2000 MHz conforming to IEC 801-3 |
| Ambient air temperature for operation | 0-60 °C |
| Product certifications | RINA, DNV, ABS, FM Class 1 Division 2, RMRS, GL, GOST, C-Tick |